Zaciski transformatorowe Energeks – rodzina zacisków TOC na tle rysunków

10 Sep

2026

Energeks

How to choose a transformer clamp? M12, M20 or M30 – matching the clamp to the transformer rating

A transformer clamp is a small part that carries the full LV current – on a 630 kVA transformer that is over 900 A per phase. If it is the wrong size, it overheats, works loose and can eventually damage the bushing. Choosing one comes down to four questions: what current flows on the LV side, what thread the bushing stud has, how many conductors you connect, and whether the clamp sits on a phase or on the neutral.

1. Work out the LV current

The rated current on the low-voltage side follows from the transformer's rated power:

I = S / (√3 × U)

S is the rated power in VA (kVA × 1000) and U the rated LV voltage – usually 400 V or 420 V for distribution transformers. Example for 400 kVA at 420 V: 400,000 / (1.732 × 420) ≈ 550 A.

2. Check the thread of the LV bushing stud

The clamp screws directly onto the bushing stud, so its internal thread must match the stud. LV bushings of oil-immersed transformers are made to EN 50386, and the stud diameter grows with the bushing current. On distribution transformers up to 630 kVA you will mostly find three sizes:

Transformer ratingLV current at 400 VLV current at 420 VStud threadClamp rating
63 kVA91 A87 AM12250 A
100 kVA144 A138 AM12250 A
160 kVA231 A220 AM12250 A
250 kVA361 A344 AM20630 A
400 kVA577 A550 AM20630 A
630 kVA909 A866 AM301000 A

The table shows the typical case, but manufacturers do not always follow it – so we always check the thread on the stud itself or in the transformer documentation (datasheet, dimension drawing). Above 630 kVA the current exceeds 1000 A and larger studs or busbar connections are used – that calls for an individual selection.

TOC-1 transformer clamp screwed onto an LV bushing stud

TOC-1 clamp screwed onto the LV bushing stud of a MarkoEco2 transformer.

3. Count the conductors per phase

Horizontal clamps take two main and two auxiliary conductors per phase. For TOC clamps that means:

  • main conductors: 2 × 95–240 mm² (RE, RM, SM conductors) or 2 × 300 mm² RMC – aluminium or copper,
  • auxiliary conductors: 2 × 2.5–50 mm² – e.g. for metering, the substation's auxiliary supply or an LV surge arrester.

Conductor codes: RE – solid round, RM – stranded round, SM – stranded sector-shaped. The conductors go straight into the sockets and are clamped by screws, with no crimped cable lugs. Grid operators see it the same way – the Polish DSO TAURON Dystrybucja, in its standard for MV/LV transformers, specifies LV clamps for direct conductor connection without crimped lugs, in a cable or a busbar version.

Cable size and number are the designer's call – based on current-carrying capacity, installation method, voltage drop and short-circuit conditions. The clamp has to physically accept them. If you need more than two main cables per phase, or the transformer is connected to the LV switchgear by busbars, choose a busbar clamp. See our overview of types of transformer clamps.

4. Phase or neutral – /U and /N versions

One transformer needs a set of four clamps: three for the phases and one for the neutral. In the TOC series, /U is the phase clamp and /N has an extra stud (two on TOC-2/N) for the neutral or earthing conductor or an earthing strip. Some operators require that a 25 × 4 mm earthing strip can be connected to the neutral clamp – Energa-Operator's requirements for MV/LV transformers are one example. TOC clamps in the /N version allow this.

TOC-1 or TOC-2?

Both clamps share the same thread, current rating and connection capacity – they differ in shape and in how much room they take on the tank cover.

TOC-1TOC-2
Designbody with offset foot, two locking screws under the headcompact head, slotted stem, locking screws on the side
When to choosethick cables, easy access to the socketsLV bushings close together, little room on the cover
Catalogue no.DP 5100–5300, DP 5100N–5300NDP 6100–6300, DP 6100N–6300N

Product pages: TOC-1 transformer clamp and TOC-2 transformer clamp.

Selection in practice – three examples

  • 160 kVA, two 120 mm² cables per phase: M12 stud, approx. 231 A → 3 × DP 5100 + 1 × DP 5100N (TOC-1).
  • 400 kVA in a container substation, little space between bushings: M20, approx. 577 A → 3 × DP 6200 + 1 × DP 6200N (TOC-2). How to select the transformer itself for such a station is covered in how to select an MV transformer for a container substation.
  • 630 kVA, two cables per phase as per design: M30, approx. 909 A → 3 × DP 5300 + 1 × DP 5300N (TOC-1).

What to include in your enquiry

  • transformer rating and type, or the LV stud thread,
  • number and size of cables per phase, plus auxiliary conductors,
  • version: TOC-1 or TOC-2 (if unsure – we will advise),
  • whether you need OZNN insulating covers,
  • number of sets and delivery date.

The full range is in our transformer clamps category. We ship clamps from stock in Poland – separately or fitted to a MarkoEco2 transformer before dispatch. How to install a clamp so that it does not overheat is explained in why transformer clamps overheat.

Energeks transformer clamps – in stock in Poland
Tell us the transformer rating and cable sizes – we send the quote the same day.Request a quote

Reviews

No reviews!

Rating*
This site is protected by reCAPTCHA and the Privacy policy and Terms of use from Google apply.